EM Lock Wiring with Identix K30: Terminal Pins, Exit Button and Power

Step-by-step wiring of a fail-safe EM lock and exit button to the Identix K30 access terminal, using the terminal pin layout, with safety notes.

Short answer: for a fail-safe EM lock, feed +12 V from the power supply into COM1, take NC1 to the lock’s +, and connect the lock’s − to GND. Wire the exit button between BUT and GND. Power the lock from a separate access-control power supply rather than the terminal.

Always follow the wiring label and manual supplied with your unit. Work with power off. If you are not comfortable with low-voltage wiring, ask an installer.

K30 lock terminal pins

From the Identix K30 wiring diagram supplied with the unit:

PinLabelWire colourUse
1GNDBlackGround
212VRed12 V DC
3GNDWhiteGround (exit button return)
4BUTGreenExit button input
5NO1BlueRelay normally open
6COM1GrayRelay common
7NC1PurpleRelay normally closed

Why NC for an EM lock?

An EM (magnetic) lock holds the door only while powered — it is fail-safe. The relay’s NC contact stays closed (lock powered, door held) and opens for a few seconds when a valid user is verified, cutting power so the door releases.

An electric bolt that is fail-secure would use NO1 instead — check the lock’s manual.

Wiring steps

  1. Power supply +12 V → COM1 (pin 6).
  2. NC1 (pin 7) → EM lock +.
  3. EM lock − → power supply GND, common with the terminal’s GND.
  4. Exit button: one terminal to BUT (pin 4), the other to GND (pin 3).
  5. Power the K30 from its own adapter or the supply’s terminal output as per the manual.
  6. If the lock has no built-in back-EMF protection, fit a diode across the lock as its manual specifies.

Settings

In the device menu set the lock open time (for example 3–5 seconds) and test: verified user → click → door releases → relocks.

Safety checks

  • Connect the fire-alarm release so the lock drops on alarm.
  • Use a supply with battery backup if the door must stay locked during power cuts — but ensure emergency exit is always possible.
  • Fit a break-glass or emergency release on exit routes as required for the building.

Related: EM locks, exit buttons, biometric door access.

Reviewed by Adapt Security Systems technical team.